Our industry is engaged in an important dialogue to improve the efficiency and resilience of real assets through transparency and industry collaboration. This article is a contribution to this larger conversation and does not necessarily reflect GRESB’s position.
How rethinking outdoor air, filtration, and air cleaning can cut HVAC energy without compromising indoor air quality.
Many buildings pay twice for the outdoor air they bring inside. They pay first in energy, cooling and drying that air, and sometimes reheating it, before it ever reaches occupants. Then they can pay again in air quality, because the same intake that delivers outdoor air can also carry in traffic exhaust, fine particles, and wildfire smoke.
Please note that outdoor air in this context is often referred to as “fresh” air. Given that over 80% of cities globally have outdoor air exceeding the WHO PM2.5 guideline of 5 micrograms per cubic meter, this article does not use the term “fresh” air but the more appropriate term “outdoor air.”
For real estate owners working toward decarbonization targets, that double cost is an overlooked opportunity. Treating ventilation, filtration, and air cleaning as a single system can reduce HVAC energy use and emissions while keeping indoor air healthy.
The hidden energy cost of outdoor air
Conditioning outdoor air takes substantial energy. In hot, humid climates, incoming air must be cooled and dehumidified, and sometimes reheated afterward. As extreme heat becomes more frequent, that burden grows. Cutting unnecessary outdoor-air treatment, while maintaining acceptable indoor air quality, can lower both operating costs and the emissions tied to them.
Outdoor air is not always clean air
Ventilation is essential, but outdoor air is not automatically clean. Traffic emissions, fine particulate matter, industrial pollution, and wildfire smoke can all enter through the outdoor air intake. That creates a difficult trade-off: bringing in more outdoor air can raise both conditioning loads and the amount of pollution entering the building. A performance-based approach resolves this by considering outdoor air quality, indoor sources, filtration, and air cleaning together.
Using ASHRAE 62.1 to plan smarter ventilation
ASHRAE Standard 62.1 gives designers an alternative to relying only on prescriptive ventilation rates. Its Indoor Air Quality Procedure (IAQP) lets them design around contaminant sources, target concentrations, air cleaning effectiveness, and occupant acceptability. Where codes permit it and the design is properly documented, effective air cleaning can support a design that uses less outdoor air.
Better filtration without the fan-energy penalty
Higher-efficiency mechanical filters capture more particles, but some designs also add significant resistance to airflow. In existing air-handling units, that extra pressure drop can force fans to use more power or reduce the air delivered. AtmosAir dielectric barrier discharge bipolar ionization (DBD BPI) offers another path. Installed within the HVAC system, it works alongside conventional filters to enhance particle removal.
Peer-reviewed evidence for a lower-energy approach
A 2025 study by Deify Law and Elbert Ho, published in the ASME Journal of Engineering for Sustainable Buildings and Cities, compared three configurations: MERV 13 filtration alone, MERV 13 combined with AtmosAir DBD bipolar ionization, and a stand-alone HEPA system. Under the study’s controlled conditions:
- PM2.5 removal: 85% for MERV 13 alone, 97% for MERV 13 with DBD BPI, and 99.7% for HEPA.
- Calculated power consumption: approximately 239 W for MERV 13 with DBD BPI, compared with 411 W for HEPA.
- Filter pressure drop: 224 Pa for MERV 13 with DBD BPI, compared with 398 Pa for HEPA.
Under the study’s test conditions, the combined system came within three percentage points of HEPA-level particle removal while using about 42% less power.
Planning for measurable decarbonization
Building owners can bring ventilation and filtration into their carbon-reduction plans with a disciplined, four-step sequence:
- Establish a baseline. Measure outdoor-air volumes, HVAC electricity use, humidity, and indoor pollutant levels.
- Review the requirements. Evaluate the IAQP alongside local code requirements.
- Assess the options. Compare air cleaning technologies and lower-resistance filters.
- Verify the results. Confirm performance with continuous monitoring and energy measurement.
Useful metrics include PM2.5, representative VOCs, CO₂, temperature, relative humidity, fan power, and cooling loads. Any ionization application should also be evaluated for potential byproducts and verified under actual operating conditions.
A more integrated path to lower-carbon buildings
The goal is not simply to minimize outdoor air or maximize filtration. It is to deliver acceptable indoor air quality with the least practical energy use. By combining the right ventilation strategy, effective air treatment, careful filter selection, and ongoing verification, building owners can support occupant well-being and reduce operational emissions at the same time. For portfolios pursuing decarbonization, this integrated approach is a practical, measurable addition to the plan. The air a building breathes does not have to cost twice.
References
Law, Deify, and Elbert Ho. “Effect of Nonthermal Plasma Technology on Reducing Airborne Contaminants in an Indoor Setting.” ASME Journal of Engineering for Sustainable Buildings and Cities 6 (2025): 024501. https://doi.org/10.1115/1.4068505.
ASHRAE. ANSI/ASHRAE Standard 62.1, Ventilation and Acceptable Indoor Air Quality (applicable edition; Indoor Air Quality Procedure).
ASHRAE. ANSI/ASHRAE Standard 52.2, Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size.
This article was written by Sam Michael, General Manager at AtmosAir Asia. Learn more about AtmosAir here.